HOME Project Maintenance

Daily check items

Solar cell array

Solar cell array information
Inspection type Check list Inspection tips
Visual inspection Contamination and damage to the surface No significant contamination or damage.
Adrenal glands and rust on supports No corrosion and rust.
Damage to external wiring (connection cable) There should be no damage to the connecting cable.

Junction box

Junction box information
Inspection type Check list Inspection tips
Visual inspection Corrosion and damage to the enclosure No corrosion and rust.
Damage to external wiring (connection cable) There should be no damage to the connecting cable.

Inverter

Inverter Inpormation
Inspection type Check list Inspection tips
Visual inspection Corrosion and damage to the enclosure No corrosion or rust, and the first part is not exposed.
Damage to external wiring (connection cable) There must be no damage to the cables connected to the inverter.
Check ventilation (vents, ventilation filters etc.) Vents must not be blocked.
Noise, odor, smoke generation and abnormal overheating There should be no abnormal noise, abnormal vibration, odor and abnormal overheating during operation.
Indication of abnormality in the display There should be no abnormal codes or lamps indicating an abnormality on the display unit.
Development status There should be no abnormality in the development status of the display part.

Storage battery

Storage battery Inpormation
Inspection type Check list Inspection tips
Visual inspection Discoloration, deformation, expansion, damage, liquid level drop, temperature rise, odor, rust, loose terminals, etc. Do this while power is supplied to the load.

Periodic inspection

Solar cell array

Solar cell array Inpormation
Inspection type Check list Inspection tips
Visual inspection Connection of ground wire and relaxation of connection terminals The grounding wire must be securely connected. There must be no loosening of the screw.

Junction box

Junction box Inpormation
Inspection type Check list Inspection tips
Visual inspection Corrosion and damage to the enclosure No corrosion or damage
Damage of external wiring and loosening of connection terminals There should be no abnormality in wiring and no loosening of screws
Damage of ground wire and loosening of connection terminal There should be no abnormality in the ground wire, and there should be no loosening of screws
Measurement
and Exam
Insulation resistance <Solar cell module-ground wire> 0.2MΩ or more, measured voltage DC 500V (measured for each circuit) <between output terminal and ground>1MΩ or more, measurement voltage DC 500V
Open voltage It must be the specified voltage and the polarity must be correct (measured for each circuit)

Inverter

Inverter Inpormation
Inspection type Check list Inspection tips
Visual inspection Corrosion and damage to enclosure No corrosion or damage
Damage of external wiring and loosening of connection terminals There should be no abnormality in wiring and no loosening of screws
Check ventilation (ventilation hole, ventilation filter, etc.) Damage to ground wire and loosen connection terminal There should be no abnormality in the ground wire, and there should be no loosening of screws
Check ventilation (vents, ventilation filters, etc.) Vents should not be blocked
Abnormal sound, odor and vibration during operation There should be no abnormal sound, vibration, or odor during operation
Measurement
and Exam
Insulation resistance (between inverter input/output terminals and ground) 1MΩ or more, measuring voltage DC 500V
Check the operation of the display unit (display unit display, generated power, etc.) There should be no abnormality in the display status and development status
Timer operation test for input blocking time The inverter will start automatically after a certain period of time after stopping

축전지

축전지 정보
Inspection type Check list Inspection tips
Visual inspection Discoloration, deformation, expansion, damage, drop in liquid level, temperature rise, odor, rust, loose terminals, etc. Do this while power is supplied to the load

Maintenance cycle

Module

Module Inpormation
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Module wiring O O
Diode O O
Frame O O
Color, discoloration O O
PIC, Hot sopt O O

Junction panel

Junction panel Inpormation
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Ventilation structure O O
Unbolt O O
Diode O O
Replacement of life cycle parts such as fuse O O

Inverter

Inverter Inpormation
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Ventilation structure O O
Unbolt O O
Fan behavior O O
Replacement of lifecycle parts such as capacitors O
Dust removal O O

Switchboard

Switchboard information
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Ventilation structure O O
Unbolt O O
trans overheat O O
Dust removal O O

Cable

Cable information
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Wind twist O O
Wire heating O O
Connection status O O

Structure

Structure Information
Item Years 1-3 Years 4-6 Years 7-9 10+ years
Unbolt O O
Sink O O
Corrosion O O

Compare project alternatives

Inspection items before use of solar power generation facilities

Solar cell

Solar cell
Item Content Inspect
Appearance check Solar cell discoloration and damage
Check for leaks, corrosion, and damage to the insulation of the terminal block
Check the electrical connection (equipotential bonding) between the solar cell and the support
Electrical property test Maximum output
Open voltage
Short-circuit current
Maximum output voltage and current
Fill rate
Power conversion efficiency
Array Insulation resistance
Ground resistance

Power converter

Power converter
Item Content Inspect
Appearance check Whether power converter is installed
Check for abnormalities in switchboard (protection and control) instruments, alarm devices, etc.
Check the insulation interval of the switchboard and the wiring status of the wiring
Check grounding location and connection status
Insulation resistance Measure the insulation resistance between the circuit and the ground after opening the input/output switch of the power converter
Dielectric strength For new equipment, the test is omitted by checking the test report
Control circuit and alarm device Check alarms by simulating various protection and control functions
Static switch automatic/manual transfer test Check the automatic/manual switching between the power control unit and the static switch from the setting value presented by the manufacturer or the testing institute
Reverse operation control test If solar power generation fails or the generated power is insufficient to supply the load, check whether there is insufficient power supply from the grid
Independent driving prevention test Check the state of disconnection of the linkage by the independent operation prevention function so that it is not fed back to the distribution line in the event of a power outage on the KEPCO line
Power converter automatic/manual transfer test Auto/manual transfer test is performed to check whether there is an abnormality in the power converter in operation or the state of uninterrupted transfer with the power converter in standby in case of overload
Charging function test Check the contents of the capacity test conducted at the factory, select the charging mode arbitrarily, and check whether the operating values ​​such as voltage and current can be varied for each charging mode

Power conversion facility protection device

Power conversion facility protection device
Item Content Inspect
General specification Check name plate and test report
Capacity of power converter
Appearance check Check for damage or damage to the protective device enclosure
Check whether the installation status is appropriate
Insulation resistance Protecting deviceㅣ Measuring insulation resistance between terminals and ground
Test guard Whether or not power generation facilities are stopped or power is cut off to prevent reverse transmission in the event of a power outage in the KEPCO grid
Check the electrical equipment protection device and operation status when various abnormal conditions such as overvoltage and overcurrent of solar cell power generation facilities occur
accumulator Check facility status
Check electrolyte
Ventilation status

Comprehensive interlocking test

Comprehensive interlocking test
Item Content Inspect
Check overall interlock drawing Check drawing
On-site installation Check the inlet, switchgear and parking breaker interlock
Check interlock between parking breaker and low voltage circuit breaker
Check interlock of low voltage circuit breaker and power converter